Application: Heat flow meter
Installation site: Return line
Calibration: Approval according to MID 2)
Cable: 1.5 m between counter and flow meter
Power supply: Battery 3.6 VDC (D cell) 11 years battery life (replaceable)
Energy unit: kWh (without decimal places) for Qp 0.6-6.0 m3/h, MWh (to 2 decimal places) for Qp 10.0-60.0 m3/h
Temperature sensor type (pair): Pt 500 / 2 m cable
Ø temperature sensor: 5.2 mm
Temperature sensor installation: 1 sensor installed directly in flow meter, Qp 0.6-2.5 m3/h, 2 free sensors for Qp ≥ 3.5 m3/h
Measurement cycle: 4 sec.
Other models available with respect to: size; models with cold meter, heat flow meter with cold tariff or solar; communication; sensor variants upon request; request specification sheet.
Please note: Pricing information for heat flow meter without calibration fee / fee for conformity assessment!
Flamco has been involved in the development, production and sale of high-quality components for use in HVAC systems since 1956. It is part of the stocklisted Aalberts NV, instituted in 1975. Along with Comap, which helps manage water and energy through its thermal and sanitary products that increase comfort in buildings, the Aalberts hydronic flow control business unit was constituted. Stronger together, Flamco and Comap will continue to build mission critical technologies to manage heating and cooling humanly with better financial and environmental efficacy. From source to emitter we partner with our customers to engineer seamless energy efficient hydronic systems for their building requirements.
comap.aalberts-hfc.com | aalberts-hfc.com
Stay up-to-date. Subscribe to our newsletter.
I agree to the processing of my personal data. Aalberts hydronic flow control attaches importance to your privacy.